CC-Link Safety System Remote I/O Unit for Light Curtain SF-CL1T264T
CC-Link Safety System Remote I/O Unit for Light Curtain

SF-CL1T264T

SPECIFICATIONS

Designation CC-Link Safety system I/O unit with connectors for light curtain
Model No. SF-CL1T264T
Connectable light curtain SF4B series
Applicable standard IEC 61508 SIL3
Control category ISO 13849-1 (EN 954-1, JIS B 9705-1) Category 4
Unit power
(Note 2)
Supply voltage 24 V DC±10 % Ripple P-P 10 % or less
Current consumption 140 mA or less (24 V DC, with all points ON)
Input specifications No. of input points
(Note 3)
Input of light curtain: 2 points
(with interference prevention function)
Input of terminal block: 6 points
(input terminals: 12 points)
Rated input voltage 24 V DC
Rated input current 4.6 mA approx.
Response time OFF → ON: 0.4 ms or less
(at 24 V DC, excluding connecting device),
ON → OFF: 0.4 ms or less
(at 24 V DC, excluding connecting device)
Safety remote station
input response time
32 ms or less + filter-out time
(1 ms, 5 ms, 10 ms, 20 ms, 50 ms)
Output specifications No. of output points 4 points (source + sink type), 2 points (source + source type)
Rated load voltage 24 V DC
Rated load voltage range 24 V DC±10 % Ripple P-P 10 % or less
Max. load current 0.5 A / point
Output type Source + sink type, Source + source type
Response time OFF → ON: 0.4 ms or less (at 24 V DC),
ON → OFF: 0.4 ms or less (at 24 V DC)
Safety remote station
input response time
32 ms or less
External power
supply
(For external
device)
(Note 3)
Voltage 24 V DC±10 % Ripple P-P 10 % or less
Current 60 mA
(24 V DC, with all points ON, excluding external load current)
Wiring method for
common
16 input points / common, 4 output points / common
(Terminal block 2-wire type)
Common current Max. 4 A (Total of inputs and outputs)
No. of stations occupied 1 station
Ambient temperature 0 to + 55 ℃ + 32 to + 131 (No dew condensation),
Storage: -140 to + 75 ℃ -140 to + 167
Overvoltage category
Pollution degree 2
External connection system Terminal block, 2 crimp-style terminals or less
Cable 0.3 to 2.0 mm2
Applicable crimp-style
terminal
RAV1.25-3 (Conforming to JIS B 2805)
(Applicalbe wire size: 0.3 to 1.25 mm2)
Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were ambient temperature +20 ℃ +68 .
2) The power supply connected to this product must satisfy the following conditions:
1 SELV (Safety Extra Low Voltage):
Reinforced insulated from hazardous potential part (48 V or more)
2 Compliance with the LVD (Low Voltage Directive)
3 Output voltage within 21.6 V to 26.4 V DC (Ripple P-P: 10 % or less.)
3) Total number of input points is 8 points, and use 2 points for control output (OSSD 1, 2) of 2 light cutains. Two inputs terminals are assigned for each input since dual wiring is supported.